A study on the negative sequence current injection during LVRT of IBRs

Authors

  • A. Blázquez Department of Electrical Engineering ESI-Bilbao, University of the Basque Country (UPV/EHU) Plaza Ingeniero Torres Quevedo 1, 48013 Bilbao (Spain) Author
  • M. Larruskain Department of Electrical Engineering ESI-Bilbao, University of the Basque Country (UPV/EHU) Plaza Ingeniero Torres Quevedo 1, 48013 Bilbao (Spain) Author
  • E. Torres Department of Electrical Engineering ESI-Bilbao, University of the Basque Country (UPV/EHU) Plaza Ingeniero Torres Quevedo 1, 48013 Bilbao (Spain) Author
  • P. Eguia Department of Electrical Engineering ESI-Bilbao, University of the Basque Country (UPV/EHU) Plaza Ingeniero Torres Quevedo 1, 48013 Bilbao (Spain) Author
  • A. Castañon ZIV Parque Tecnológico 210, 48100 Zamudio (Spain) Author
  • R. Cimadevilla ZIV Parque Tecnológico 210, 48100 Zamudio (Spain) Author

DOI:

https://doi.org/10.52152/4528

Keywords:

IBR, Grid Code, LVRT, Negative Sequence, Line Protection

Abstract

Low Voltage Ride Through (LVRT) behaviour of Inverter Based Resources (IBR) during asymmetrical grid faults is dictated by the requirements of Grid Code (GC) at the Point of Common Coupling (PCC) of the renewable energy plants. Earlier GCs demanded only positive sequence current injection, which gave freedom to inverter manufacturers to implement different negative sequence injection strategies, while newer GCs define specific negative sequence current injection requirements. The existence of different negative sequence current control strategies during grid faults creates problems for line protection relays, as fault detection algorithms malfunction for certain angle relationships between the negative sequence voltage and current phasors.

This paper analyses different negative sequence injection algorithms of IBRs and demonstrates certain relationships between sequence impedances of the inverter that can be used for improving line protection algorithms. The analytical findings are confirmed via Real Time simulations of a Type 4 wind farm connected to a power system with different network strength characteristics.

Downloads

Published

2025-07-25

Issue

Section

Articles