Implementation of a New Method for an Improved Voltage Dips Evaluation by the Italian Power Quality Monitoring System in Presence of VT Saturation Effects
DOI:
https://doi.org/10.24084/repqj08.383Abstract
The paper deals with a recent measurement
improvement introduced into the Italian power quality monitoring
system, concerning voltage dips detection and their proper
evaluation in the presence of voltage transformer VT saturation
phenomena. Saturation effects, essentially on network operated
with isolated neutral, can give origin to “false” voltage dips, which
can affect the on-line voltage monitoring during a few specific
events (i.e. single line-to-ground faults). The “false dip” problem,
on the other hand, can be considered negligible in compensated
neutral networks.
A new criterion has been developed in cooperation with the
Polytechnic of Turin, based on the detection of a second harmonic
component in the measured voltages, which, once provided with
the proper setting parameters, can succeed in identifying “false”
dips. The criterion effectiveness has been evaluated on field. The
major advantage of the filter implementation in the monitoring
system is that, from now on, network operated with isolated
neutral could be considered quite similar to those operated with
neutral compensation from the point of view of voltage dip
performance.