Centralized normalization of harmonic voltages by the third-order passive filter
DOI:
https://doi.org/10.24084/repqj08.365Abstract
The values of harmonic voltages at network
nodes should meet the standard limits. Harmonic voltages can
be decreased to admissible values on a centralized basis. The
paper addresses the problem of centralized decrease of
harmonic voltages in the high voltage networks with distributed
nonlinear loads using third-order passive filters. Mathematical
expressions to determine parameters of the third-order passive
filter are given. The parameters of the selected filters for 220
kV network supplying traction substations with power and also
the estimates of the efficiency of work of these filters for
different network configurations are presented as an example.
The efficiency of the C-type and third-order filters are
compared.