Calculation of involved energies in thermal plasma at the opening of high voltage breakers

Authors

  • A. Ziani Author
  • H. Moulai Author
  • A. Nacer Author

DOI:

https://doi.org/10.24084/repqj13.487

Keywords:

Electric arc, High voltage, Arc plasma

Abstract

Usually, calculations of involved energies in thermal plasma at the opening of high voltage breakers are led by using dimensional type models (1D, 2D and 3D) founded on assumptions sufficiently precise. This survey deals with the determination of temperature and thermal transfers of arc plasma quenching in a high voltage breaker by coupling a 0D (time dependent) arc model with the heat equation. This approach enabled to refine the thermal balance and to evidence the particular importance of the thermal radiation. Also, investigations are focused on the influence of the deionisation constant of the extinguisher gas on the plasma conductance and temperature variations which are checking parameters of the extinction. The obtained results are in good agreement with measurements performed by other authors.

Author Biographies

  • A. Ziani

    Laboratory of Electrical and Industrial Systems,

    FEI, USTHB,BP 32 Bab Ezzouar, Algiers, 16311, Algeria.

    Phone/Fax number:+ Tel. 00213 771415065, e-mail: ziani08@yahoo.fr

  • H. Moulai

    Laboratory of Electrical and Industrial Systems,

    FEI, USTHB,BP 32 Bab Ezzouar, Algiers, 16311, Algeria.

    Phone/Fax number:+ Tel. 00213 771415065

  • A. Nacer

    Laboratory of Electrical and Industrial Systems,

    FEI, USTHB,BP 32 Bab Ezzouar, Algiers, 16311, Algeria.

    Phone/Fax number:+ Tel. 00213 771415065

Downloads

Published

2024-01-16

Issue

Section

Articles