Comparison of Chilled ceiling and Mixing ventilation assisted by intermittent personalized ventilation: Thermal comfort and Energy savings

Authors

  • D. Al Assaad Author
  • K. Ghali Author
  • N. Ghaddar Author

DOI:

https://doi.org/10.24084/repqj18.370

Keywords:

Personalized ventilation, chilled ceiling, mixing ventilation, thermal comfort, energy savings

Abstract

The integration of intermittent personalized ventilation in office spaces equipped with chilled ceiling and mixing ventilation has been proven to enhance comfort and provide energy savings. However, the performance of the intermittent personalized ventilation has not been compared between both systems. This is important to see under which system the intermittent personalized ventilation performs best. In this work, two office spaces equipped with a chilled ceiling/mixing ventilation coupled with intermittent personalized ventilation were modelled using validated CFD models. The intermittent jet was supplied towards an infected occupant at an average flow rate of 7.5 L/s. The frequency of the intermittent PV was varied in each case. It was found that the intermittent personalized ventilator provided better thermal comfort in the case of chilled ceiling under neural to warm conditions (14% increase compared to MV systems). However, twice as much energy savings were obtained in the case of mixing ventilation than chilled ceilings. Therefore, it is better off to operate intermittent PVU under MV systems

Author Biographies

  • D. Al Assaad

    Department of Mechanical Engineering American University of Beirut.Lebanon

  • K. Ghali

    Department of Mechanical Engineering American University of Beirut.Lebanon

  • N. Ghaddar

    Department of Mechanical Engineering American University of Beirut.Lebanon

Published

2024-01-12

Issue

Section

Articles